Why my analog module do not sense the incoming current...?

why my analog module do not sense the incoming current from sevral tansmitters because i measured the current entering the analog channels and there was a current (4-20mA)
but no reading i got on the display communicating with the analog module

Answer:
What is the make and model of your analogue module. Maybe with that info an answer can be found.
However, if your analogue module can measure both current and voltage, ensure that it has been rightly set to measure current. In addition, some analogue modules measure different current levels ie 0 - 1 mA and 4 - 20mA. Thus, also ensure that you have set the module to measure the correct current level.

Hope this helped
I find lot of possibilities in this..

1.u r measurig ac or dc...is u are measuring dc keeping in ac mode then there would be no indication.
2.did u connect the current measuring device in series or parallel..if so connect it in series..?may be this is the reason y ur fuse has blown out.
3.Check for current rating of fuse and ur analog module.
4.Most importantly can be loading effect or impedance matching.
5.Check for deadband.It will not work if it is less than 4mA.

I think these all can be reasons are some may be the reasons.Hope this would help

The answers post by the user, for information only, FunQA.com does not guarantee the right.



More Questions and Answers:
  • My ac unit leaks?
  • What are common equipments used in waste water treatment plant?
  • What would be the type of power inverter that I would need to power a 15 amp, 120 volt AC lawnmower?
  • Who are the local installers and affectionados and suppliers in milton fl area of solar electricity systems?
  • Is it possible to generate energy with a peltier plate ?
  • Circuit Design?
  • What is your opinion about the Hutchinson affect?
  • Where can i find informations about microwave radio?!?
  • What is the cost of Electricity per UNIT in Mississauga, Ontario, Canada or Ontario, Canada.?