Can I run a 4-20 mA (24 volt) signal and a 110 signal on the same conduit?

I am using a multi-pair wire and I am sending a 4-20 mA signal as well as an 110 digital input signal to a PLC. Thanks

Answer:
From a product and electrical safety standpoint, I would not recommened sending both signals down a single multipair cable. I would suggest a seperate cable for each signal.

24V is not considered a hazardous voltage so any product powered from 24V signal has been designed assuming minimal threat if a operator or service person has access to that voltage.

110V on the other hand, is a hazardous voltage often supplied by a battery source which may or may not be current limited. Should a short result between the 24V and 110V the end product may not provide adequate protection to a user, or service person. Or the device may catch fire under fault.

Crosstalk is frequency dependant not voltage dependant, but if high frequencies are involved, shielding the cables will likely be required.
With the disparity in voltage levels you may have an issue with the 110 interfering with (cross talk) the 24 v. I would run them in the same conduit as long as one of the signals is carried by a shielded cable.
It is never recommended.

If the 4-20 cable is shielded and you are doing it in your home where no one will see it you might get away with it from a signal-noise point of view.

Commercially it would not be accepted and mixing the high and low voltage would violate even the residential Code for sure.
I would not but most of the time the shielding will let you get away with it. It depends on the length of the run as well a long run means more chances for trouble. I had trouble once in a cable tray where the AC was feeding a cheap DC motor control. The temperature gage was jumping just enough to cause some process problems. Another problem I had is when a wire got hot and melted the low voltage wire to the high voltage wire. It blew the tar out of the input card.
The National Electrical Code in the United States says that wires in the same conduit must have the same temperature and voltage rating. So it would be a violation to have a 300 V rated cable and a 600 V rated cable in the same conduit. Other than that, if signal interference isn't a problem, then its OK.

The answers post by the user, for information only, FunQA.com does not guarantee the right.



More Questions and Answers:
  • Optical Engineering with no physics in high school?
  • Why does the release of compressed air make a can cold?
  • What is "elastic modulus" ?
  • We use value of 141.5 and 131.5 in the calculation of API gravity. How these values have determined?
  • I need to find good credible articles about the proliferation of nucler power in developing countries. Anyone?
  • Can a microwave magnetron emit a positive charge?
  • Help in robotics!?
  • If the full form of dc is direct current then we say its dc current? it becomes direct current current!?
  • Hey is it true that electrical branch (e&e) is the toughest in engineering??